Đầu dò khí CO BOSCH FCC-380

Trang Chủ >> Báo cháy-Báo trộm >> Báo cháy BOSCH >> Đầu dò khí CO BOSCH FCC-380
Mã số:13040044
Đầu dò khí CO BOSCH FCC-380

Đầu dò khí CO BOSCH FCC-380

-       Đầu dò khí CO loại 4 dây.

-       Nguồn điện cung cấp từ 9-32VDC, tương thích với hầu hết các bộ báo cháy trung tâm có nguồn cung cấp 12 và 24VDC.

-       FCC‑380 Carbon Monoxide Detector (Macurco CM‑E1)

-       Solid state sensor provides maintenance-free operation

-       Microcomputer control provides virtual automatic operation

-       9 VDC to 32 VDC operation is compatible with 12‑V and 24-V systems

-       Can quickly test CO sensor on site

-       Three-color LED status display

-       Four‑wire technology for connection to any UL Listed control panel

 

The FCC380 Carbon Monoxide (CO) Detector (Macurco CM-E1) detects CO concentrations in the air at or below the UL 2034 sensitivity limits for CO exposure and before symptoms of CO exposure appear. It alerts personnel to possible exposure through audible and visual alarms. Install the detector in rooms adjacent to areas where CO concentrations are expected (garages or furnace rooms). Prime application locations include work areas or bedrooms.

Note: Do not install the detector in areas where CO concentrations are expected (garages or furnace rooms). The detector is not designed to detect smoke, fire, heat, or other gases (combustible or non-combustible).

 

Functions

LED Display

The FCC380’s three-color visual LED display indicates status and contamination level. A green display indicates the detector is operating normally. An amber display indicates a system trouble. A red display indicates dangerous CO levels.

Alarm System Operation

The FCC380 can function as part of an alarm system and connects to an alarm control panel through either a normally-open or normally-closed initiating circuit. If the carbon monoxide detector is connected to an alarm control panel, the control panel must provide an alarm for CO that is distinct from alarms for fire or intrusion.

Stand-Alone Alarm Operation

The FCC380 can function as a stand-alone device using its internal alarm (repeated loud tone bursts during alarm and chirps if sensor trouble is found). Stand-alone operation was not evaluated by Underwriters Laboratories.

 

Installation/Configuration Notes

Compatibility Information

The carbon monoxide detector is compatible with all UL Listed control panels that have 12 VDC to 24 VDC power and alarm initiating circuits. The detector can also be used with a UL Listed Class 2 power supply.

Mounting Considerations

Mount the detector 4 ft to 5 ft (1.2 m to 1.5 m) above the floor. It can be surface mounted or flushmounted on a 2inch (5.1 cm) by 4inch (10.2 cm) single-gang switch box with a minimum depth of 1.5inch (3.8 cm). Space the detectors at 30 ft (9 m) separation and do not place detectors in corners or within 5 ft (1.5 m) of a cooking appliance.

 

Temperature (operating)

+40°F to +100°F (+4.4°C to +37.8°C)

Color

White

Dimensions (H x W x D)

5.125 in. x 3.125 in. x 1. 5 in. (13 cm x 8 cm x 3.8 cm)

Weight (shipping)

1 lb (0.45 kg)

Alarm

 

Relay Configuration

one NO or NC SPST (no polarity)

Relay Rating

100 mA, 40 VDC

Sound Level

85 dBA at 10 ft (3 m)

Relay Configuration

one NC SPST (no polarity)

Relay Rating

100 mA, 40 VDC

Alarm Current

35 mA at 9 VDC to 32 VDC

Normal Current

15 mA at 9 VDC to 32 VDC

Voltage input

9 VDC to 32 VDC

-       Bảo hành: 12 tháng.

Giá: Vui lòng gọi

Số lượng :

Thêm vào giỏ Mua ngay


Chia se tren Facebook
Sản phẩm liên quan

Tel:(028) 7300 1535
Showroom:92K Nguyễn Thái Sơn - Phường 3 - Q.Gò Vấp - Tp.HCM
Website:www.sieuthivienthong.com
Email:info@sieuthivienthong.com